Laboratory & Analysis


Maintenance and Asset Management are becoming increasingly important. The aim is to reduce the costs for replacement and repair and to increase the lifetime of your capital goods. Also unexpected breakdowns should be avoided under all circumstances. Beside the early determination of possible malfunctions a very important aspect is the reduction of maintenance and repair costs.

High reliability is equal to an increase in efficiency and profitability.

Insulation Oil is considered to be one of the weakest points on a transformer. This perception must be considered in any maintenance concept. The lifetime of transformer oil is not equal to the lifetime of a transformer itself. There are several predictive maintenance techniques to take that into account and determine the condition of the insulation oil.

The most known measurements are:

  • Dielectric strength testing
  • Loss factor measurement in oil
  • Water content measurement accord. to Karl Fischer
  • Total gas content measurement
  • Dissolved gas analysis

All these parameters will give you a clear understanding of the overall condition of your transformer oil.

Oil Sampler Kit for Oil Sampling

434591614723d057e4f84ce3ce075986

Contamination-free Oil Sampling according to standards – with the Oil Sampler Kit

  • no contamination with the ambient air
  • ease of use
  • auto registration the oil temperature
  • Measurement according to standard IEC 567 and ASTM 3612

Data sheet

Total gas content

3927e79597e6a899016163cc98349bc3

Automatic analysis of the dissolved gases in oil-filled transformers

The analysis is done in 2 steps which guarantee a very high selectivity and sensitivity of the determination of dissolved gases:

  • Gas separation by means of fully vacuum degassing ( accord. to DIN EN 60567, DIN IEC 599 and IEEE C57.104-1991) and display of results
  • Option: Subsequently to the determination of the total gas content a gas chromatographic analysis can be made

Data sheet

Mobil GC/1A – Dissolved gas analysis

c3cf461ec7fc8789d1f3631ce817dd50

Mobil GC/1A – Fault gas analysis of 9 gases

Basic device with Windows control software for evaluating documentation and customer-specific settings, with Expert System for automatic Faultdiagnosis in Insulating Oils.

Data sheet

Mobil GC/2 – Dissolved gas analysis

c3cf461ec7fc8789d1f3631ce817dd50

Mobil GC/2 – Fault gas analysis of 11 gases
DIN / IEC 60567/567

Basic device with Windows control software for evaluating documentation and customer-specific settings, with Expert System for automatic Faultdiagnosis in Insulating Oils.

Data sheet

TOP TOGA – GC

f1fc09f58e30e51e490901d43df48e40

Dissolved Gas Analysis with automatic degassing unit According to IEC 567/ASTM 3612

Features and Benefits:

  • Fully automatic procedure
  • One touch operation
  • Multi-periodic vacuum degassing
  • Full TOGA analysis (11 gases)
  • Automatic transfer of gas sample

Data sheet

TOP – TOGA Autosampler

6891db805542a789c5637e09d6e2d5ec

The TOP-TOGA Autosampler is an easy-to-use and rugged sample tray for full vacuum degassing of transformer oil samples. It is designed for optimum value, time saving and excellent performance. There is no more need for changing sample containers; once the oil sample is taken from the transformer, plug your syringe into the sample tray – absolutely contamination-free! Allows for analysis of 16 oil samples unattended!

  • 16 syringe sample capacity
  • Fully automatic procedure
  • Automation for processing all samples unattended
  • Interchangeable sample tray for 100 and 50ml glass syringes
  • Contamination-free with integrated rinsing steps
  • Rugged construction and simplicity of design
  • Integrated calibration facility

Data sheet

Pocket Titrator KF

cc68206f73a2a8b5b734b84dd17fc0cf

The versatile coulometer – simple titrating!

  • The Pocket Titrator KF is a truly portable and easy to use coulometric titrator: Titrations with electrochemical reagent generation – simple by one “click” in the user-friendly software.
  • The microprocessor with high performance controls automatically all electrolysis adjustments. The titration rate is adjusted automatically to electrolysis current amount to be titrated.
  • PocketTitrator can be used for various applications: precise and fast, compact, lightweight and robust. Using for Karl Fischer titration and determination of the bromine index ideal

Data sheet

SIGMA 2000 Interfacial Tensiometer

63836751cb0be2e68f3ed14e195bef8e

The SIGMA 2000 interfacial tensiometer is a fully automatic device for the measurement of interfacial tension in transformer oil accord. to ASTM-D971 and IEC60422. No previous knowledge of IFT measurement is required, the step-by-step instruction on the large LCD display guides you through the measurement process and ensures fail-safe measurement every time. Measurement in transformer oil made easy.

  • Accord. to ASTM-D971 and IEC60422
  • Requires no knowledge of IFT measurement
  • Step-by-Step instructions
  • Large LCD display
  • Immediate display of data on screen

Data sheet

 

Aqua 40.00

b5c8d877053ab9fb3bc24e35e7b3daed

Aqua 40.00 with Heating module

The basic module is the essential device for microcoulometric water determination according to Karl-Fischer-Titration in liquid samples and gases. This coulometric titration is based on the electrochemical generation of the iodine needed for the determination.

Data sheet

 

Tan Delta Test Set – TDM 4000

aee56808466799ed1947ac7670f98c2d

 

Automatic Dielectric Constant Tan Delta & Resistivity
Test Set –TDM 4000

The TDM-4000 is an automated instrument for measuring the electrical characteristics of transformer oil, insulating liquids & other insulating material samples. The TDM-4000 measures Capacitance, Dielectric Constant (Î), Dielectric Loss, Tan Delta (Dissipation Factor), Resistance & Resistivity of the test sample. The Tan Delta value gives an indication of the condition of the oil sample. There are several reasons due to which the Tan Delta value may be affected – such as moisture, dissolving of some of the transformer varnish, insulating material deteoriating etc.

TDM-4000 is especially designed to work with the IEC & ASTM type oil cell with a 2mm spacing and will apply a stress in the range of 100-1200 volts per mm as recognized by ASTM and other specifications.
Data sheet